Coleman Equipment Book (M)

VRF

Line Set Sizing Guide - Outdoor to Y-Branch

Line Set Sizing Guide: Y-Branch to Indoor Units

Indoor Unit 6K-15K*

Indoor Unit 18k-60k

*When length from Multi branch kit to indoor unit exceeds 49 feet, upsize liquid line from 1/4" to 3/8"

C/HVAHP036 C/HVAHP048 C/HVAHP060

C / E / D F / H / G

A

3/8"

3/8"

3/8"

1/4"

3/8"

B

5/8"* 5/8"* *Upsize Gas pipe to 3/4" when length exceeds 328 feet. 5/8"*

1/2"

5/8"

*Line Set Length Requirements and Allowances

Model

C/HVAHP036 C/HVAHP048 C/HVAHP060

Max. Total Piping Max. Pipe Length from Outdoor to Indoor Unit Max. Height Diff. between Indoor Units Min. Straight Pipe Required Before and After Y-Branch Min. Pipe Length Required from Outdoor to 1st Y-Branch Max. Pipe Length from 1st Y-Branch to Indoor Unit

15 Ft.

15 Ft.

15 Ft.

131 Ft.

131 Ft.

131 Ft.

24" of Straight Pipe Before and After Y-Branch must be installed before any bends.

984 Ft.

984 Ft.

984 Ft.

492 Ft.

492 Ft.

492 Ft.

49 Ft.

49 Ft.

49 Ft.

All pricing subject to change. More products and information at JohnstoneSupply.com & the OE Touch mobile app. 080123EB.01

Made with FlippingBook - Online catalogs