VRF

Example System Layout Single Zone System - 1 Outdoor w/1 Indoor

Illustrations are for reference only & do

not replace installation manuals

A

B

Line Set Sizing Guide

HVAHP036 HVAHP048 HVAHP060

A

3/8"

3/8"

3/8"

B

5/8"*

5/8"*

5/8"*

*Upsize Gas pipe to 3/4" when length exceeds 328 feet.

*Line Set Length Requirements and Allowances

Model

HVAHP036 HVAHP048 HVAHP060

Minimum Required Maximum Allowed

15 Ft.

15 Ft.

15 Ft.

492 Ft. 131 Ft.

492 Ft. 131 Ft.

492 Ft. 131 Ft.

Max Height Outdoor-Indoor

• VRF Outdoor Unit Requires its own Circuit Breaker for Power, while the Indoor Units must be Powered from a Second Circuit Breaker Don’t Forget! • If you have an AP Air Handler w/Strip Heat added, this unit will require its own dedicated circuit breaker